For larger substations and
the most complex applications

Introduction

The most powerful member of the Orion family, the OrionLX+ takes on all automation applications in T&D substations. Modular serial cards and network options enable the OrionLX+ hardware to leverage existing equipment and minimize upgrade effort. The OrionLX+ has been tested with very large configurations and confirmed to be suitable for the largest substations: 40,000 points, 256 IEDs, redundancy, and IEC 61850

Hot Swappable
Power Supplies

Single or redundant supplies can be ordered, each removable under power from the
front of the OrionLX+. For higher reliability, both power supplies share the load, and are
health monitored by internal Orion diagnostics.

Expanded
 Networking Options

Five NovaCard Expansion Cards are available to support a wide range of network and I/O needs:

NovaCard #0 (NC0): Adds one 10/100/1000BaseT Ethernet port and 4DI/4DO:

 

NovaCard #1 (NC1): Adds one 10/100/1000BaseT Ethernet port, two SFPports,and4DI/4DO:

 

NovaCard #2 (NC2): Adds 12 10/100/1000BaseT Ethernet ports:

 

NovaCard #3 (NC3): Adds PRP/HSR ports for LAN A and LAN B (10/100/1000BaseT and SFP) plus one 10/100/1000BaseT Ethernet port and one SFP port. Also adds 4 DI / 2 DO:

 

NovaCard #4 (NC4): Adds 16 DI:

Front View
of LX+

Other Hardware
 Features

Keyboard and mouse ports

Modular, field-replaceable serial port cards

Serial Cards

A: RS-232 Standard w/IRIG-B
B: RS-422/485
C: ST-Fiber Optic
D: Bit Card (Bit-to-byteconversion)
E: RS-232 Isolated w/IRIG-B
G: RS-485 w/IRIG-B
H: V-Pin Fiber Opticw/IRIG-B

IED Protocols

ABB DPU
Allen Bradley DF1
Areva Optimho
DNP3 SAv5 (Secure Authentication)
IEC 60870 101/103/104
IEC 61850
Modbus
PG&E 2179
SEL® ASCII
SEL® Fast Meter
SEL® Fast Operate
SEL® Fast SER
SPA Bus
TransData DTO


Plus Client versions of SCADA protocols: CDC, Conitel, Harris, L&G 8979 and Tejas

IRIG-B

Standard Built-In

SCADA Protocols

FTP and sFTP
HTTPS
ICCP
LDAP
MultiSpeak NTP and SNTP
PTP (Precision Time Protocol)
RADIUS
SNMP
telnet
XML


Plus suite of other security protocols

Back Plate
Features

Specifications

Environmental

Operating Temperature / Storage Temperature
-40°C to +70°C / -40°C to +85°C
Operating Humidity
5 to 95% non-condensing

Physical

Standard case (2U)
19W x 3.5H x 13D (in)
Weight
9.5 lbs

Available SFP Transceivers

ModelConnectorModeDistanceWavelengthSpeed
SFP-MM01LCMultimode550m850nm1Gbps
SFP-MM02LCMultimode2km1310nm100mbps
SFP-SM01LCSingle mode10km1310nm1Gbps
SFP-SM04LCSingle mode40km1310nm1Gbps
SFP-RJ01RJ45Copper100mN/A1Gbps

Performance/Capabilities

IED/SCADA Points
40,000; (typical)
Refresh Rate
< 2 sec; typical

Data Archiving & Storage

Memory
8GB
Database
PostgreSQL

Digital Inputs on NC0 / NC1

Quantity
4 DI, isolated
Input Range
12-48V dc / 120-250V dc
1ms time-stamped

Digital Outputs on NC0 / NC1

Quantity
4 DO with 2 Form A, 2 Form C
Contact Ratings
10A MOV protected

Digital Inputs on NC3

Quantity
4 DI, grouped
Input Range
12-48V dc / 120-250V dc
1ms time-stamped

Digital Outputs on NC3

Quantity
2 DO with 1 Form A, 1 Form C
Contact Ratings
10A MOV protected

Digital Inputs on NC4

Quantity
16 DI, isolated
Input Range
12-48V dc / 120-250V dc
1ms time-stamped

Alarm Output

Type
Form C
Contact Ratings
10A MOV protected

Power Supplies

Input Voltage
HV Supply:
125/250V dc nominal and
120/240V ac nominal +/- 20%
LV Supply:

24/48V dc nominal +/- 20%

Power Required

HV Supply:
DC: Typical 30W, max 50W
AC: Typical 60W, max 75W
LV Supply:
DC: Typical 30W, max 50W

Warranty

10 Year Limited

Let’s talk